Modern IT systems are now managed by complex and intelligent shadow systems that manage all of the IT system-related infrastructure measures like UPS solutions, temperatures, access controls, power switches and the like. With its selected range of add-ons for the SITEMANAGER 6 and SITEMONITOR 6, GENEREX offers the ideal system solution for modern and lean infrastructure management.

偵測器套件搭配 環境管理控制器 SITEMANAGER 6

溫度偵測器 —— Temperature sensor

Ord. No.: SM_II_T

The ambient temperatures should be monitored when operating a UPS solution, regardless of where the batteries are located because operating them outside the specifications can permanently damage the system and the batteries and, in extreme cases, even result in fires. With the temperature sensor, you can monitor the facility in real time and receive a warning, in due time, if the operational temperatures are concerning.

Measurement Range: 0°C – +100°C, +/- 1%
Power Supply Voltage: 15 – 24V DC
Output Signal: 0 – 10V DC
Additional Inputs: 1x Digital
Special Features: Connection for other sensors
Connection Cable: RJ12/6_5, 5m, (Included) max. 50m
Dimensions: 70 x 70 x 27 mm (W x L x H)

數位式溫度偵測器 —— Digital Temperature sensor

Ord. No.: SM_II_T_DIG

The SM_II_T_DIG is a digital temperature sensor that uses a slightly different query method to transfer its measurement data to the SITEMANAGER 6.
SM_II_T_DIG – the digital version of the SM_II_T temperature sensor.

Measurement Range: -25°C – +100°C
Power Supply Voltage: 15 – 24V DC
Output Signal: One wire
Special Features: Connection for other sensors
Connection Cable: RJ12/6_5, 5m, (Included) max. 50m
Dimensions: 70 x 70 x 27 mm (W x L x H)

溫度與相對濕度偵測器 —— Temperature and Relative Humidity(可單獨使用)

Ord. No.: SM_II_T_H

Depending on the location of a facility, humidity can develop in the area around batteries that can settle on electrical lines, the batteries or the UPS solution. Both measurement results can be independently combined with other sensors via a sensor matrix to automate a variety of responses to the environment.
The SM_II_T_H offers temperature and humidity, but requires 2 ports.

Measurement Range / Temperature:0°C – +100°C, +/- 1%
Measurement Range / Humidity: 0 – 100% rel. H, +/- 5%
Power SupplyVoltage: 15 – 24V DC
Output Signal: 2x 0 – 10V DC
Additional Inputs: 1x Digital
Connection Cable: RJ12/6_5, 5m, (Included) max. 50m
Dimensions: 70 x 70 x 27 mm (W x L x H)

交流電壓量測器 —— VMC converter

Ord. No.: SM_II_VMC

Current fluctuations can result in undesired responses, such as restarts, in the systems downstream from a UPS solution and can damage equipment. The SM_VMC is a sensor with which you can consistently check the quality of the output of a UPS system.
The SM_VMC is used to measure the voltage via a provided power supply unit and send it to the CS141/BACS/SM6 via SENSORMANAGER for monitoring.

Measurement Range: 160 – 260V (AC, True RMS)
Power Supply Voltage: 15 – 24V DC
Output Signal: 0 – 10V DC
Special Features: Measurement via accompanying power supply
Connection Cable: RJ12/6_5, 5m, (Included) max. 50m
Dimensions: 70 x 70 x 27 mm (W x L x H)

淹水與高濕度偵測器 —— Water and High Humidity

Ord. No.: SM_II_HYG2

The SM_II_HYG2 is required when humidity from evaporation, condensation water or cloud formation or the like, which results in a UPS system’s operating conditions being exceeded, is expected in the operating environment.
The difference in comparison to the SM_II_T_H is that the SM_II_HYG2 can also directly report water penetration.

Measurement Range: wet or dry
Power Supply: 9 –15VDC
Current Consumption: ca. 20 mA
Contact Load: 125 VAC,60 VDC,1A
Type of Contact: NC o. NO (configurable)
Connection Cable: RJ12/6_5, 5m (Included) max. 50m
Dimensions: 70 x 70 x 27 mm (W x L x H)
Special Features: 1 sensor (Included) with cable length 2m, acoustic and optical (LED) alarm, connection option for up to 10 additional SM_HYG2

SM_II_HYG2 擴充套件

Ord. No.: SM_II_HYG2

The SM_II_HYG2 can be connected via the SITEMANAGER and can, alternatively, work in stand-alone mode as a water detector with its own alarm transmitter and an independent power supply unit. The sensor probe for the water sensor can be delivered with a 5m or 10m sensor cable upon request.
Ord. No.: SM_HYG_S
Water sensor with a cable length of 2m/78.74in.
Ord. No.: SM_HYG_S5
Water sensor with a cable length of 5m/196.85 in.
Ord. No.: SM_HYG_S10
Water sensor with a cable length of von 10m/393.7in.
Ord. No.: PS_HYG
Power supply for using the SM_HYG2 as a standalone version.

偵測器套件應用於門禁與防盜等系統

The UPS solution is a particularly important target within infrastructures because they secure the operation of critical systems until other emergency systems can take effect. GENEREX therefore offers active access control systems to respond quickly to unauthorized entry:

玻璃門窗破裂偵測器 —— Glass breakage detector

Ord. No.: SM_II_GLAS

The SM_II_GLAS glass breakage detector is a fast and efficient way of ensuring the security of glazed surfaces and immediately outputting a digital alarm in the event of cracks.
The SM_II_GLAS can be combined with other sensors via a sensor matrix.

Measurement Range: Radius ca. 2m
Type of Contact: NC
Frequency range: 120 kHz
Connection Cable: RJ12/6_5, 5m (Included) max. 50m
Dimensions: 27 x 27 x 14 mm (W x L x H)

入侵偵測器 —— Motion Detector

Ord. No.: SM_II_MD

With the SM_II_MD motion detector, rooms, access routes, hallways or escape stairwells can be quickly and efficiently monitored. As soon as the SITEMANAGER 6 receives a report of movement, any scenario can be realized, from an automated lighting system through to a complex reporting and warning system.
The SM_II_MD can be combined with other sensors to create complex access controls.

Measurement Range: 14m x 14m, 90°
Power Supply: 9 – 16 V DC
Output Signal: Same as power supply
Current Consumption: ca. 17 mA
Connection Cable: RJ12/6_5, 5m (Included) max. 50m
Dimensions: 115 x 60 x 45 mm (W x L x H)

門窗防盜偵測器 —— Electrical Door Contact

Ord. No.: SM_II_DC

The SM_II_DC is not an electrical lock; it is a supporting measure within the building management system. For instance, an alarm system can only be armed if all of the windows are closed.
The SM_II_DC can be combined with other sensors to create complex access controls.
Type of Contact: Magnetic Alarm Contact
Connection Cable: RJ12/6_5, 5m (Included) max. 50m

氣體偵測器、閃光警報器和警報蜂鳴器

SITEMANAGER 6s can initiate “emergency measures” to, for instance, output evacuation alarms for hazardous areas, switch on emergency ventilation systems or inform superordinate or subordinate systems.

警報蜂鳴器 —— Alarm Transmitter

Ord. No.: SM_II_BUZ

The SM_II_BUZ is an alarm transmitter that can be dynamically coupled to the alarm behavior of all sensors and digital contacts. The alarm signal can be used to make people aware of hazards.
The SM_II_BUZ alarm transmitter can be combined with other sensors and contacts.

Power Supply Voltage: 12 – 15V DC
Current Consumption: ca. 30mA
Sound Level: ca. 85 dB
Connection Cable: RJ12/6_5, 5m (Included) max. 50m
Dimensions: 70 x 70 x 27 mm (W x L x H)

閃光警報器 —— Optical Alarm Transmitter

Ord. No.: SM_II_FLASH

The SM_II_FLASH outputs a clearly visible alarm light to, e.g. make people aware of hazards, indicate machine operating states or, in conjunction with other systems, indicate an acute danger.
The optical SM_II_Flash alarm can be coupled with all sensors and inputs.

Power Supply Voltage: 12-15V DC
Current Consumption: ca. 170mA
Connection Cable: RJ12/6_5, 5m (Included) max. 50m
Dimensions: 70 x 70 x 67 mm (W x L x H)

偵測器套件應用於氣體與有害物質等環境

Based on production conditions, toxic, fatal or highly explosive gas mixtures may develop. Gas sensors are often the only option for detecting these sometimes odorless and colorless hazards in time and taking automatic countermeasures.

煙霧偵測器 —— Smoke Detector

Ord. No.: SM_II_SD1

When fire protection regulations require, these sensors must secure facilities or flammable areas. Even without this statutory requirement, this sensor is recommended because the earlier the warning, the faster suitable measures can be taken in response.
The smoke detector reliably detects acute smoke development. It can also be coupled to the measurement results of other sensors and contacts which makes this sensor very flexible.

Power Supply Voltage: 10 – 15V DC
Output Signal: Same as power supply
Current Consumption: ca. 50mA
Detection: Photoelectric chamber
Anschlusskabel: RJ12/6_5, 5m (Included) max. 50m
Abmessungen: 84 x 77 mm (D x H)

氫氣偵測器 —— Hydrogen Sensor

Ord. No.: SM_H2_LC

Hydrogen typically forms as a by-product of the charging process of batteries and is released into the environment via valves or open cases. Since it is much lighter than the surrounding air, it rises and collects on overhangs, in shelves, niches, ceiling areas, etc. As soon as the hydrogen concentration reaches about 4%, an unstable and highly flammable gas mixture will be formed up. Since hydrogen itself is odorless and colorless, you need specialized sensors like the SM_H2_LC require hydrogen sensors with which hydrogen can be detected at an early stage. The hydrogen sensor SM_H2_LC has a two-stage warning system in which the warning levels are triggered independently of one another. When used with the SITEMANAGER 6, the SM_H2_LC is placed directly on the digital inputs in order to receive a corresponding warning signal.

Power Supply Voltage: 9 – 112V DC (stabilized)
Current Consumption: ca. 300mA max.
operating temperatur: 0 – 40 C
measurement accuracy: +/- 20% under calibration condotions (20 C, 1013 hPa, hum. 65%)
Max. measurable instantaneous hydrogen concentration: 100% LEL (<1min/30min)

電流偵測感應器

A UPS solutions depends on the quality of the batteries. They are subject to a natural aging process over time so the whole system’s performance decreases. The internal quality of the discharging/charging currents in the UPS solution can be monitored using the GENEREX current sensors.

交流暨直流偵測器 —— AC & DC Current Sensors

Current sensors for measuring AC and DC charging/discharging simoultaneously at BACS. At SENSORMANAGER /SITEMANAGER 6 this device measures AC or DC, depending on the configuration. Diameter 40mm/1.57in.Pluggable system, BACS addressing through DIP SW and at SENSORMANAGER /SITEMENAGER 6 AC or DC configurable through DIP SW. The more flexible design allows subsequent installation into existing high voltage AC systems. A hinge allows opening the upper ring to simplify inserting the power cables. Retrofitting with this hall sensor is quick and cost-effective: The fold-out ring makes the installation work easier and extensive conversions unnecessary. Including connection cable RJ12/6_5,

Ord. No.: SM_CSH50
AC & DC Current Sensor 50A
Ord. No.: SM_CSH200
AC & DC Current Sensor 200A
Ord. No.: SM_CSH400
AC & DC Current Sensor 400A
Ord. No.: SM_CSH1000
AC & DC Current Sensor 1000A
Ord. No.: SM_CSH2000
AC & DC Current Sensor 2000A

第三方其他廠家偵測器

The SENSORMANAGER can also manage and link sensors from third-party suppliers. If you need sensors that require

  • pressure conditions
  • gas concentrations
  • light conditions
  • acid/base concentrations

or the like, ask us:

Together, we will find a customized solution to secure your IT and building infrastructure.